Case Study: Art Institute of Chicago, Loggia Restorations

Arne P. Johnson, Principal
08:49
 

During stone balustrade maintenance at the Art Institute of Chicago's south loggia, severe corrosion of underlying steel members was discovered. Field exploration found that corrosion and section loss from long-term water infiltration extended several feet from the ends of the beams, through a heavily loaded region below a stone plinth.

Learn about WJE's innovative structural repair approach and the laboratory testing regime that verified its performance. This project received a 2024 Excellence in Structural Engineering Award from SEAOI.